Mini Cable Fault Locator
Fault Distance Range : 300 m, 1 km, 3 km
Measurement Mode : Auto
Fault Measurement Accuracy : ± 1% ± 1 m
Pulse Width : 30 nsec to 3msec
Pulse Waveform : Square
Pulse Amplitude : 24 V pp
Cable Constant (VOP) range : 50 to 150 m/μs
Measurement dead zone : 1 meter
Auto Measurement dead zone : 15 meter
Output Impedance : 50
Sampling Speed : 50
Gain Range Control : 1:10
Display Readout : LED Display
Power Supply : 12 V rechargeable battery 3.2 Ah Capacity built in charger
Timer : Built in timer automatically switches off after 5 minutes to save the battery power
Weight : About 1 Kg
Dimensions : 205 mm x 160 mm x 54 mm approx.
Accessories : Operation/Service manual, Mains cable, Output cable, Carrying case
Environmental Spec. : Operation: 0 C to 50 C, Storage: -10 C to 60 C
Working Temperature : 0 C to 55 C