TemperatureUses PT100 Precision Temperature Sensor
Limit Setting2 Nos. 10 Turn Precision Trimpots On Front Panel
Recorder Output0-2V For The Selected Range
Supply110V AC/220V AC ± 15% Internally Selectable
SizeFront Fascia - 96mm X 96mm
CabinetFlame Retardant Grade Plastic Enclosure
Features
Precision indication of conductivity
Automatic Temperature Compensation
4 Step Range selection 0.1μs to 199.9ms
2 independent Set Points with High and Low logics for on-line control
Front Panel ‘touch type’ membrane switch to read the limits set
Voltage corresponding to Conductivity available for external recorder
‘Cell Adjust’ on front panel for calibration.
Range
a. 199.9μs
b. 1999μs
c. 19.99ms
d. 199.9ms
The range is selectable from the rear and can be calibrated by ‘Cell Adj’ at the front for individual range.
Compensation
The Compensation is internally set at 2% per ˚C
NOTE: If PT100 is not available, then fix a simulated resistance of PT100 @ 25˚C approx. 110Ω. Instrument will not work otherwise.